The performance of complementary feeders, running in parallel, is significantly improved by installing STS (Static Transfer Switch) at critical locations. Normally, it is assumed for STS control logic that the terminal voltages are in phase and both feeders should have identical impedances. This paper evaluates the performance of STS for feeder reconfiguration having disparity in line impedances and phase angles. Control logic for the fast operation of STS has been proposed. To validate the performance of the STS and its control logic, two feeders with different lengths, diversity in consumers and non-homogenous conductor have been considered. When the preferred feeder violates operational limits, control logic of STS provides fast transfer of the sensitive loads to alternate feeder. PSCAD/EMTDC package has been used for simulation and analysis.