220V/50Hz residential circuit was taken as application object. Series arc fault experiment platform was built with reference to the domestic existing research results and the United States UL1699 standards. Arc current and arc voltage were collected. High order harmonic ratio analysis method for wire’s current was proposed. Through the variation condition analysis for high order harmonic ratio of wire’s current data in parallel multi-load circuit, the variation characteristics, for high order harmonic ratio caused by arc fault, was summed up. Research results show that: if a non-linear load was connected to the circuit’s load in parallel, when this two loads were in stable operation at the same time, high order harmonic ratio of wire’s current increased. If a linear load was connected to the circuit’s load in parallel, high order harmonic ratio of wire’s current did not significantly change. When arc fault occurred in parallel load circuit, high order harmonic ratio of wire’s current appeared to rise sharply, and it is not stable, in fierce fluctuation.