Overvoltages developed in the termination of a transmission line at energisation.

Author(s)
M. Amin Electrical Engineering Department, University College of Engineering, Taxila, Pakistan
Abstract
The transient voltage developed across the capacitance at the end of a transformer feeder or at the end of a line containing a series reactor, following line energisation, has been calculated in the presence of source impedance. The Laplace Transform and Travelling Wave technique has been used for analysis and the transient voltage has also been observed on a physical model. Voltages of 5 pu are predicted when there is fundamental frequency resonance in the termination, as may occur for lines up to 10 km long. For third and fifth harmonic resonances, voltages approximately 0.5 pu and 1.0 pu below this are found but they may occur in lines upto 50 km long. Source impedance greatly reduces the voltage developed, for example either adding 20011 resistance or 0.02H inductance results in a peak voltage approximately half that obtained for an infinite source. The effectiveness of using closing resistors to reduce the voltage is confirmed, and it is clear that very pessimistic estimates of overvoltage will result if an infinite source is assumed.
Publication Details
Page(s) 7-14
DOI DOI not available
Published Journal: Journal of Engineering and Applied Sciences, Volume: 6, Issue: 2, Year: 1987

Request the full text from PASTIC