Abstract
Evaluation of discharge gas cooling system of a natural gas compressor station was studied. Scale deposition potential and corrosion forming tendencies of the cooling water were monitored. Plant operating at high Holding Time Index contributed towards increased scale forming potential of cooling water Corrosion data analysis showed slightly high rate of corrosion of cooling water tarot may he due to improper management of acid dosing in the system. Absence of side stream filtration unit might have supported increased turbidity in the system that helped increased growth of microbial colonies in the water. Cooling water quality standards did not support in keeping balance between corrosive and scale harming potential of the circulating water. Therefore, improved limits of cooling water quality standards have been suggested in this work.
Publication Details
Page(s) 21-25
DOI DOI not available
Published Journal: Journal of Chemical Society of Pakistan, Volume: 31, Issue: 1, Year: 2009