No Detail Found!

Performance Enhancement Of An Industrial Fire Tube Boiler

Author(s)
M.Z.U. Haq Department of Chemical Engineering, NFC Institute of Engineering & Fertilizer Research, Faisalabad, Pakistan ; Research & Development Department, NFC Institute of Engineering & Fertilizer Research, Faisalabad, Pakistan
Z. Yahya Department of Chemical Engineering, NFC Institute of Engineering & Fertilizer Research, Faisalabad, Pakistan; Research & Development Department, NFC Institute of Engineering & Fertilizer Research, Faisalabad, Pakistan
H.M. Masood Department of Chemical Engineering, NFC Institute of Engineering & Fertilizer Research, Faisalabad, Pakistan
N. Ali Department of Chemical Engineering, NFC Institute of Engineering & Fertilizer Research, Faisalabad, Pakistan
M. Ashraf Department of Chemical Engineering, NFC Institute of Engineering & Fertilizer Research, Faisalabad, Pakistan Research & Development Department, NFC Institute of Engineering & Fertilizer Research, Faisalabad, Pakistan
Abstract
An Industrial boiler is considered as highly energy intensive equipment. The primary objective of this study is to identify and quantify the potential losses of different energy sections of the fire tube boiler and its overall performance. Several energy saving measures such as combustion optimization, excess air control, control of flue gases temperature and effect of excessive or uncontrolled steam blowdown optimization, on the overall performance of boiler are also applied. Energy as a result of energy saving measure has been determined as well. In present study, some main causes of energy wastages are summed up, by using an energy auditing. From the results of energy audit, the boiler's thermal energy efficiency and combustion efficiency are found to be 70.09% and 75.70% respectively. The boiler overall energy efficiency from 70.09% to 73.27%. It was also observed that these losses can be reduced by controlling stack temperature, excess air and optimized blowdown. There covered energy can be utilized to preheat the combustion air and feed water. Economic evaluation of energy saving measures in annual fuel resulted savings of 6.3 Million PKRs without any investment but only improving working methodologies. As a result of these efforts, the savings in terms of cost has also been determined.
Publication Details
Page(s) 43-48
DOI DOI not available
Published Journal: Journal of Pakistan Institute of Chemical Engineers, Volume: 48, Issue: 1, Year: 2020

Request the full text from PASTIC

Keywords
Stack Gas, Steam, Blowdown, Boiler Efficiency, Steam Boiler
0

Citations

0

Downloads

65

Views