This study was conducted at I-9 treatment plant, Islamabad to analyze the physicochemical assessment of various parameters and heavy metals concentrations in wastewater and to check the wastewater treatment plant efficiency. Therefore composite wastewater samples were collected from influent, effluent and external streams. Their results were compared with Maximum permissible limits (MPL) of Pakistan Environmental Protection Agency (PakEPA). The results of influent, effluent and external stream of wastewater samples are: pH ranged from 6.2 to 6.9, 6.4 to 6.9 and 6.8, EC ranged from 840 to 1250, 830 to 930 and 700 to 890 (µS/cm), Total dissolved solids ranged from 570 to 850, 570 to 630 and 480 to 600 mg/l, total suspended solids ranged from 0.062 to 0.09, 0.008 to 0.42 and 0.068 to 0.069 mg/l, Fluoride ranged from 0.4 to 4.7, 0.8 to 3.5, 1.2 to 2.9 mg/l, Chloride ranged from 48 to 180, 56 to 71 and 44 to 55 mg/l, respectively. Heavy metal concentrations were analyzed by using Atomic Absorption Spectroscopy (AAS) and were found that iron ranged from 0.16 to 2.94, 0.75 to 2.055 and 2.673 to 3.374 mg/l and manganese ranged from 0.193 to 0.579, 0.1 to 0.861 and 0.407 to 0.85 mg/l. Similarly, zinc ranged from 1.9 to 2.7, 1.8 to 2.5 and 2.3 to 2.8 mg/l and Ni ranged from 1.19 to 1.66, 1.15 to 1.56 and 1.11 to 1.21 mg/l. Likewise, lead ranged from 0.32 to 0.6, 0.15 to 0.65 and 1.1 to 1.2 mg/l, chromium ranged from 1.04 to 1.1, 1.06 to 1.11 and 1.1 to 1.11 mg/l, cadmium ranged from 0.2 to 0.4, 0.13 to 0.38 and 0.3 to 0.8 mg/l, respectively. Results of some parameters like nickel, lead, chromium and cadmium were found above the permissible limits of Pak-EPA. So it is recommended that Waste water should be treated at industrial territory. Only treated water should be allowed to drain into Lai stream.
Publication Details
Page(s) 16-20
DOI DOI not available
Published Journal: International Journal of Economic and Environmental Geology, Volume: 8, Issue: 4, Year: 2017

Request the full text from PASTIC

Keywords
Heavy metals, Wastewater, Physicochemical parameters, treatment plant, PAK-EPA
0

Citations

0

Downloads

65

Views