On 24th September, 2006 at about 13:43 hours, a severe disturbance occurred on the National Grid System of Pakistan which caused cascading outage of transmission lines and generating stations leading to its total collapse. This major blackout was one of the worst power system failures of WAPDA, the main electric utility ofPakistan, in this decade. This paper provides an insight of the investigations to find out its possible root cause(s) and the remedial measures to prevent such blackouts in future. The bulk power transfer on long transmission lines in northern part of WAPDA, prior to system blackout, had already stressed the power network very heavily close to its stability limits. As a result, the system, following a disturbance, was stressed further beyond its capability and experienced small signal and voltage instabilities which ultimately led to its total collapse. In this paper, detailed analytical work including power flow and eigenvalue analyses.